The classification of hazardous areas of global main explosion-proof system and corresponding protection methods
Hazardous Locations Marking Examples
Markings for Global IECEx System/for China
The classification of hazardous areas of global main explosion-proof system and corresponding protection methods
Hazardous Locations Marking Examples
Markings for Global IECEx System/for China
Area Classification-Division Versus Zone
Type of Area | NEC and CEC(North America) | IEC,China and CENELEC |
Continuous Hazard | Division 1 or Zone 0/Zone 20 | Zone 0/Zone 20 |
Intermittent Hazard | Division 1 or Zone 1/Zone 21 | Zone 1/Zone 21 |
Hazard Under Abnormal Conditions | Division 2 or Zone 2/Zone 22 | Zone 2/Zone 22 |
ATEX Equipment Category and IEC/IECEx Equipment Protection Level
Equipment Group |
ATEX Equoipment Category |
Environment | IEC/EN Explosion Protection Level |
Level of Protection |
Presence or Duration of Explosive Atmosphere |
Correlation with Hazardous Areas |
I | M1 | Mine (Methane, Coal dust) |
Ma | Very High | Presence | |
M2 | Mb | High | Risk of Presence | |||
II | 1 | G-Gas | Ga(for gas) Very | High | Continuous presence | Zone 0(Gas/Vapor) |
2 | Ga(for gas) | High | Likely to occur | Zone 1(Gas/Vapor) | ||
3 | Ga(for gas) | Lower | Unlikely to occur | Zone 2(Gas/Vapor) | ||
III | 1 | D-Dust | Da(for dust) Very | High | Continuous presence | Zone 20(Dust) |
2 | Da(for dust) | High | Likely to occur | Zone 21(Dust) | ||
3 | Da(for dust) | Lower | Unlikely to occur | Zone 22(Dust) |
Explosive/Flammable/Combustible Atmosphere/Environment Grouping
Division System | Zone System | ||
Typical Gas/Dust Fibers/Flyings | Canada(CEC) | Canada(CEC) | Typical Gas/Dust Fibers/Flyings |
Acetylene | Class I,Group A | Group IIC | Acetylene |
Hydrogen | Class I,Group B | Hydrogen | |
Ethylene | Class I,Group C | Group IIB | Ethylene |
Propane | Class I,Group D | Group IIA | Propane |
Methane(Mines) | Gaseous Mines | Group I | Methane(Mines) |
Metal Dusts | Class II,Group E | Group IIIC | Conductive Dusts |
Coal Dusts | Class II,Group F | Group IIIB | Non-Conductive Dusts |
Grain Dusts | Class II,Group G | ||
Fibers/Flyings | Class II | Group IIIA | Combustible Flyings |
Temperature Code & Temperature Class
Maximum Surface |
US(NEC) |
IEC,China,European |
450 |
T1 |
T1 |
300 |
T2 |
T2 |
280 |
T2A |
- |
260 |
T2B |
- |
230 |
T2C |
- |
215 |
T2D |
- |
200 |
T3 |
T3 |
180 |
T3A |
- |
165 |
T3B |
- |
160 |
T3C |
- |
135 |
T4 |
T4 |
120 |
T4A |
- |
100 |
T5 |
T5 |
85 |
T6 |
T6 |
Ingress Protection(IP)Codes
First Numeral-Protection Against Solid Bodies | |
0 | No Protection |
1 | Objects greater than 50mm |
2 | Objects greater than 12.5mm |
3 | Objects greater than 2.5mm |
4 | Objects greater than 1.0mm |
5 | Dust-Protected |
6 | Dust-Tight |
Temperature Code & Temperature Class
Maximum Surface |
US(NEC) |
IEC,China,European |
450 |
T1 |
T1 |
300 |
T2 |
T2 |
280 |
T2A |
- |
260 |
T2B |
- |
230 |
T2C |
- |
215 |
T2D |
- |
200 |
T3 |
T3 |
180 |
T3A |
- |
165 |
T3B |
- |
160 |
T3C |
- |
135 |
T4 |
T4 |
120 |
T4A |
- |
100 |
T5 |
T5 |
85 |
T6 |
T6 |
Protection Methods for Potentially Explosive Gas/Vapor Atmospheres
Second Numeral-protection Against Water | |
0 | No Protection |
1 | Vertical Dripping |
2 | Angled Dripping(15°titled) |
3 | Spraying |
4 | Splashing |
5 | Jetting |
6 | Powerful Jetting |
7 | Temporary Immersion |
8 | Continuous Immersion |
Protection Methods for Potentially Explosive Gas/Vapor Atmospheres(continue the above table)
TYPE OF |
CODE |
MARKET |
APPLICATION |
STANDARD |
PROTECTION |
General |
Ex |
IEC |
EPL Ga,Gb,&Gc |
IEC 60079-0 |
|
Incareased |
Ex e (or Ex eb) |
IEC |
EPL Gb |
IEC 60079-7 |
|
Non-Incendive |
(NI) |
US |
Class I,Division 2 |
ISA 12.12.01/FM 3611 |
No arcs |
Non-Sparking |
Ex nA (or Ex nAc) |
IEC |
EPL Gc |
IEC 60079-15 |
|
Non-Sparking |
Ex nA (or Ex nAc) |
IEC |
EPL Gc |
IEC 60079-15 |
|
Explosion-proof |
(XP) |
US |
Class I,Division 1 |
UL 1203/FM 3615 |
|
Flame-proof |
Ex d (or Ex db) |
IEC |
EPL Gb |
IEC 60079-1 |
Control the |
Enclosed Break |
Ex nC (or Ex nCc) |
IEC |
EPL Gc |
IEC 60079-15 |
|
Intrinsic Safety |
Ex ia,ib,ic Ex ia,ib,ic (IS) (IS) AEx ia AEx ib Ex ia Ex ib Ex ia,ib,ic AEx ic Ex ic |
IEC China US CA US US CA CA EU US CA |
EPL Ga,Gb,Gc EPL Ga,Gb,Gc Class I,Division 1 Class I,Division 1 Class I,Zone 0 Class I,Zone 1 Class I,Zone 0 Class I,Zone 1 Category 1G,2G,2G Class I,Zone 2 Class I,Zone 2 |
IEC 60079-11 GB 3836.4 UL 913/FM 3610 CSA C22.2 No.157 ISA 60079-11/FM 3610 ISA 60079-11/FM 3610 CSA C22.2 No.60079-11 CSA C22.2 No.60079-11 EN 60079-11 ISA 60079-11/FM 3610 CSA C22.2 No 60079-11 |
Limit energy of sparks and surface temperature |
Protection methods for combustible/ignitable dust atmospheres(including fiber and flyings)
TYPE OF PROTECTION |
CODE |
MARKET |
APPLICATION |
STANDARD |
PROTECTION PRINCIPLE |
Pressurization |
Type X,Y Type X,Y Type Z Type Z Ex px(or Ex pxb) Ex px(or Ex pxb) AEx px(or AEx pxb) Ex px Ex px (or Ex pxb) Ex py (or Ex pxb) Ex py (or Ex pxb) AEx py(or AEx pxb) Ex py Ex py (or Ex pyb) Ex pz (or Ex pzb) Ex pz (or Ex pzb) AEx pz (or AEx pzb) Ex pz (or Ex pzb) Ex pz (or Ex pzb) |
US CA US CA IEC China US CA EU IEC China US CA EU IEC China US CA EU |
Class I,Division 1 Class I,Division 1 Class I,Division 2 Class I,Division 2 EPL Gb EPL Gb Class I,Zone 1 Class I,Zone 1 Category 2G EPL Gb EPL Gb Class I,Zone 1 Class I,Zone 1 Category 2G EPL Gc EPL Gc Class I,Zone 2 Class I,Zone 2 Category 3G |
FM 3620 (NFPA 496) NFPA 496 FM 3620 (NFPA 496) NFPA 496 IEC 60079-2 GB 3836.5 ISA 60079-2 CSA C22.2 No.60079-2 EN 60079-2 IEC 60079-2 GB 3836.5 ISA 60079-2 CSA C22.2 No.60079-2 EN 60079-2 IEC 60079-2 GB 3836.5 ISA 60079-2 CAS C22.2 No.60079-2 EN 60079-2 |
|
Restricted |
Ex nR (or Ex nRc) Ex nR (or Ex nRc) AEx nR(or AEx nRc) Ex nR Ex nR (or Ex nRc) |
IEC China US CA EU |
EPL Gc EPL Gc Class I,Zone 2 Class I,Zone 2 Category 3G |
IEC 60079-15 GB 3836.8 ISA 60079-15 CSA C22.2 No.60079-15 EN60079-15 |
Keep flammable gas out
|
Encapsulation |
Ex ma,mb,mc Ex ma,mb,mc Ex ma,mb,mc AEx ma Ex ma Aex mb Ex mb AEx mc Ex mc |
IEC China EU US CA US CA US CA |
EPL Ga,Gb,Gc, EPL Ga,Gb,Gc, Category 1G,2G,3G Class I,Zone 0 Class I,Zone 1 Class I,Zone 1 Class I,Zone 1 Class I,Zone 2 Class I,Zone 2 |
IEC 60079-18 GB 3836.9 EN 60079-18 ISA 60079-18 CSA C22.2 No.60079-18 ISA 60079-18 CSA C22.2 No.60079-18 ISA 60079-18 CSA C22.2 No.60079-18 |
|
Oil lmmersion |
Ex o (or Ex ob) Ex o (or Ex ob) AEx o (or AEx b) Ex o Ex o (or Ex ob) |
IEC China US CA EU |
EPL Gb EPL Gb Class I,Zone 1 Class I,Zone 1 Category 2G |
IEC 60079-6 GB 3836.6 ISA 60079-6 CSA C22.2 No.60079-6 EN60079-6 |
|
Powder-Filling |
Ex q (or Ex qb) Ex q (or Ex qb) AEx q (or AEx qb) Ex q Ex q (or Ex qb) |
IEC China US CA EU |
EPL Gb EPL Gb Class I,Zone 1 Class I,Zone 1 Category 2G |
IEC 60079-5 GB 3836.7 ISA 60079-5 CSA C22.2 No.60079-5 EN 60079-5 |
|