TECHNICAL DATA
Specifications
| Explosion Protection: | CENELEC,IEC,NEC | Can Be Used In: | Zone 1,2 |
Product Introduction

Specification
| Global (IECEx) | IECEx (applied for) |
| Gas | Ex db eb ib [ib Gb] nC IIB T4 Gc
Ex db eb ib [ib Gb] nC IIC T4 Gc |
| Europe (ATEX) | ATEX (applied for) |
| Gas |
II 3 (2) G Ex db eb ib [ib Gb] nC IIB T4 Gc
II 3 (2) G Ex db eb ib [ib Gb] nC IIC T4 Gc |
| Certificates | IECEx; ATEX |
| Conformity to standards | EN; IEC |
Data
| Type | BKG-70/220 | BKGR-70/220 | BKG-120/380 | BKGR-120/380 | |
| Cooling capacity | W | 7300 | 7300 | 12200 | 12200 |
| BTU | 24000* | 24000* | 40000* | 40000* | |
| Heating capacity(W) | – | 7800 | – | 14500 | |
| Rated voltage/Frequency(V/Hz) | 220/50 | 220/50 | 380/50 | 380/50 | |
| Input power(P) | 3P | 3P | 5P | 5P | |
| Cooling input power (W) | 2780/12.1 | 2780/12.1 | 4380/7.8 | 4380/7.8 | |
| Heating input power (W) | ─ | 2600/11.3 | ─ | 5000/8.9 | |
| Application areas (m2) | 27~32 | 27~32 | 50~80 | 50~80 | |
| Sound level (dB) | Indoor unit | 43* | 43* | 52* | 52* |
| Outdoor unit | 53* | 53* | 56* | 56* | |
| Outline dimensions (L x W x H) (mm) |
Indoor unit | 1900 x 600 x 280* | 1900 x 600 x 280* | 1900 x 600 x 280* | 1900 x 600 x 280* |
| Outdoor unit | 870 x 850 x 319* | 870 x 850 x 319* | 1258 x 970 x 369* | 870 x 850 x 319* | |
| Control box | 380 x 250 x 165 | 380 x 250 x 165 | 380 x 250 x 165 | 380 x 250 x 165* | |
| Weight (kg) | Indoor unit | 48.00* | 48.00* | 48.00* | 48.00* |
| Outdoor unit | 75.00* | 75.00* | 119.00* | 119.00* | |
| Control box | 6.00 | 6.00 | 7.00 | 7.00 | |
| Note: 1.The above technical data is for normally supplied products of T1 (-7℃~+43℃) temperature class, rated voltage is
220V AC/50Hz, other voltages are available, such as 220V AC/60Hz, 230V AC/50Hz, 230V AC/60Hz, 240V AC/50Hz, 240V AC/60Hz, 380V AC/50Hz, 380V AC/60Hz etc., please specify when ordering. 2.The above data is only for reference, the actual product shall prevail. 3.Data with “*” are for ference, the specific kinf prevail. |
|||||
RELATED PRODUCTS
PXK(Pz) Series Explosion Proof Pressurized Cabinets Distribution Cabinets (Ex Pz IIC)
Specifications Explosio...
BKF Series Explosion Proof Wall Air Conditioners IIB Atex Approved Air Conditioning Units
Specifications Explosion Prote...
BKF(R) Series Explosion Proof Wall Air Conditioner AC (IIC) 18000 BTU 24000 BTU
Specifications Explosion Prote...
BFS Series Explosion-proof Wall-mounted Exhaust Fans
Specifications Comprehe...