BXJ Series Explosion-proof Terminal...
- ◆ Constructed with a high-strength copper-free aluminum alloy, this explosion-proof terminal boxes ensures safety by containing internal explosions and isolating the external hazardous atmosphere.
- ◆ The explosion proof enclosures treated with anti-static coating and all fasteners are anti-loosening.
- ◆ The explosion-proof control box provides centralized cabling and management, make the installation, maintenance, and inspection easier.
- ◆The IP66 rating prevents internal component of the ex terminal boxes aging and corrosion, which extends system life and lowers maintenance costs.
TECHNICAL DATA
Explosion Protection Type
- Standards: CENELEC, IEC, NEC.
- Zones: Zone 1 and Zone 2; Zone 21 and Zone 22; Class I, Zone 1 and Zone 2; Class I, Division 1, Groups A, B, C, D; Class I, Division 2, Groups A, B, C, D.
- Explosion Protection Ratings:
- IECEx (Gas and dust): Ex e IIC T6 or T5 Gb; Ex ib IIC T6 Gb; Ex tb IIIC T80°C Db IP66.
- ATEX (Gas and dust): II 2 G Ex e IIC T6 or T5 Gb; II 2 G Ex ib IIC T6 Gb; II 2 D Ex tb IIIC T80°C Db IP66.
Product Parameters
- Product Type: BXJ-e.
- Material:
- Enclosure: Copper-free Aluminium Alloy, powder coated surface.
- Exposed fastener: Stainless steel.
- Enclosure Color: Window grey (RAL7040).
- Rated Voltage: Max. 690V AC.
- Rated Current:
- Ex e: 24A (2.5mm²), 32A (4mm²), 41A (6mm²), 57A (10mm²), 76A (16mm²), 100A (35mm²).
- Ex ib: 5A (2.5mm², 4mm², 6mm²).
- Note: Ex e Rated current >125A available on request.
- Degree of Protection: IP66.
- Ambient Temperature:
- Ex e: T6 for Tamb: -50°C to +40°C; T5 for Tamb: -50°C to +55°C.
- Ex ib: T6 for Tamb: -50°C to +55°C.
- Earthing: Internal & external earthing: M6/M6.
Product Classification & Origin
- HS Code: 853650.
- Country of Origin: China.
Applicable Industries
- Explosion-Proof Terminal Boxes are specifically engineered for a wide range of industries and hazardous environments, including petrochemical, natural gas, coal, metallurgy, military, nuclear power, aerospace, firefighting, pharmaceuticals, textiles, and shipping.
- Safety Role: These boxes function as a critical link within modern industrial safety frameworks, providing physical isolation and energy control for electrical connections.
- Durability: Engineered with a robust explosion-proof structure to deliver long-lasting, corrosion-resistant performance in harsh conditions involving high temperatures, heavy dust, and corrosive gases.
Credibility
- Certifications: Warom terminal boxes meet stringent global requirements, carrying ATEX, IECEx, EAC, and other certifications.
- Performance: Features a T5-T6 temperature rating and IP66 protection to ensure reliable performance.
- Support: Warom supports projects with a seamless, end-to-end service from initial design assessment to final certification.
FAQ
- Q1: What are the principles of explosion-proof terminal boxes?
- A: Based on two main types: Flameproof (Ex d), which uses precision gaps at joints to cool flames, and Increased Safety (Ex e), which prevents arcs/sparks through enhanced insulation.
- Q2: Do the terminal boxes need regular maintenance?
- A: Yes. Critical checks include inspecting surfaces for damage, ensuring tight fasteners and intact seals, and replacing damaged parts with original factory spare parts.
- Q3: Can internal wiring be connected carelessly after installation?
- A: Absolutely not. The box only provides “containment,” and all internal electrical connections must strictly comply with electrical standards.
- Q4: Is it fully waterproof/dustproof?
- A: This depends on the IP rating. Typical boxes (such as IP66/67) resist powerful water jets or temporary immersion for reliable protection.